ATS48C66Q

Schneider Electric
ATS48C66Q
ATS48C66Q

Price: 7 126,00

Functions:

  • Deceleration (reduction in pressure surges), protection against underload or reversal of phase rotation direction
  • Control of pump priming and the pump's direction of rotation
  • Monitoring of overloads for incident detection or underloads for break detection
  • Braking for fast stop
  • Torque control on starting

Distinctive features:

  • exclusive Altistart torque control (patented by Schneider Electric)
  • constant control of the torque supplied to the motor during acceleration and deceleration periods (significantly reducing pressure surges)
  • ease of adjusting the ramp and the starting torque
  • option of bypassing the starter using a contactor 3 at the end of the starting period whilst maintaining electronic protection (bypass function)
  • wide frequency tolerance for generator set power supplies
  • option of connecting the starter to the motor delta terminals in series with each winding
  • built-in motor thermal protection
  • processing of information from PTC thermal probes
  • monitoring of the starting time
  • motor preheating function
  • protection against underloads and overcurrents in steady state
  • 4 logic inputs, 2 logic outputs, 3 relay outputs and 1 analog output
  • plug-in I/O connectors
  • function for configuring a second motor and easy-to-adapt settings
  • display of electrical values, the state of the load and the operating time
  • RS 485 serial link for connection to Modbus serial link

Additional links:

 Technical documentation and Downloads
 Request additional information and get a price quote

  • Official Supply
  • Official Warranty
  • Brand-new products only
  • Express delivery on request
Buy at: € 7 126,00

Technical Specification

Manufacturer: Schneider Electric
Series: Altistart 48
Model: ATS48C66Q
Application: pumps / fans / general purpose
Capacity, kW: -
Current, А: 660
Main power supply, V: 230-415
Phase: 3
Output frequency, Hz: 50/60
Enclosure: IP 00
Acceleration time, sec: 1-60
Deceleration time, sec: 1-60
Operation temperature, °С: -10......+40
Max. switching cycle per hour: 10
Starting current, % of rated current: 400
Integrated bypass relay: -
Control type: digital
Microprocessor supply voltage: 220-415 V
Motor protection (thermal model): +
Motor protection (input for thermistor/thermal relay): +
Motor protection (low current) : +
Motor protection (momentary motor overload): +
Motor protection (Others): +
JOG mode: -
DC braking: +
Inputs/Outputs: 4 digital inputs, 2 digital outputs, 3 relay outputs and 1 analog output
Separately adjustable parameters: 7
Mounting: Vertical position (± 10 °), in protective housing or cabinet
Network Control Protocols: Modbus
Options: The remote terminal that can be mounted on the door of the enclosure or cabinet; set of connecting cables; communication means for connecting to networks and buses Ethernet, Fipio, DeviceNet, Profibus DP